Hi Deborah a fused spur will be what the boiler needs and it will have to be 300mm away from the drainer or sink bowl. So it complies with regulations.
Hi Deborah a fused spur will be what the boiler needs and it will have to be 300mm away from the drainer or sink bowl. So it complies with regulations.
Hi Deborah Yes you need to get it moved, the regs do no allow for a socket to sit above a sink as it is considered a serious electrical hazard Hope this helps