Yes, as long as the following are adhered to 1 the circuit to be worked on it tested 2 the fused spur is in 2.5mm cable 3 the circuit is rcd protected 4 the bonding is up to current spec 10.0mm2 5 the fire does not exceed 13amps (about 3kw, or 2990 watts to be precise) Regards Wayne